Most wrong winding resistance readings are not instrument failures. They come from the connection, the temperature, or the moment someone pressed Save.
A winding resistance reading that is 3% high looks like a bad joint. A reading that keeps falling looks like a failing instrument. In practice, both are usually test conditions: a clip on a painted busbar, a winding that has not finished charging, or a temperature that was estimated instead of measured. This guide separates the factors that actually move the number.
Winding resistance is one of several tests used to assess a transformer. It can provide evidence of poor welds and loose joints, contact problems in the tap changer, broken leads and broken strands in parallel conductors, and it can indicate short circuits between turns. It is rarely conclusive on its own: a shorted turn, a mechanical deformation and a bad tap contact can produce similar-looking deviations, which is why the result is read together with ratio, excitation current, short-circuit impedance and frequency response analysis.
First, a plain definition. A winding resistance test injects a steady DC current into a winding and measures the voltage drop across it; resistance is then calculated from Ohm's law. The test is simple in principle and demanding in execution, because the quantity being measured is tiny and the winding fights back.
Two consequences follow:
The largest avoidable error in field measurement is lead and contact resistance. A two-wire measurement sends current through the same leads that sense voltage, so every clip, lug and centimetre of cable adds to the result.
R(measured) = R(winding) + 2 x R(lead) + R(contacts) [two-wire]
R(measured) = R(winding) [four-wire, within instrument accuracy]
In a four-wire (Kelvin) connection, the current leads carry the test current and the voltage leads sense only the drop across the winding. Because almost no current flows in the voltage circuit, lead resistance drops out of the result. The clamp must still make good contact, because the current path has to be stable, but its resistance no longer appears in the reading.
A transformer winding is a large inductor. When the tester applies DC, current does not step to its final value; it rises gradually, and the displayed resistance falls while that happens. A reading taken during the rise is not a measurement, it is a snapshot of a transient.
This is often described as "waiting for the core to saturate". That description is misleading. What the measurement needs is a steady current, not a saturated core. Depending on the test current and the transformer design, the core may be far from saturation and the reading can still be perfectly valid. The magnetic state does matter, because it sets the effective inductance and therefore how long the current takes to settle, but saturation is not a pass condition.
tau = L / R and settling is roughly 5 x tau
Take a winding with L = 10 H and R = 0.5 Ω. Then tau = 20 s and the current is close to steady after about 100 s. This is a first-order approximation, not a fixed test duration: L varies with test current and core magnetisation, and a large power transformer can take much longer. It explains why proper testers show a charging state instead of a number, and why forcing an early reading produces a low value that looks like a fault.
Practical rules that follow from this:
Choosing a test current is a four-way compromise, not a single setting:
Two failure modes are common. Too low a current leaves the reading noisy and slow to settle, particularly on large windings. Too high a current shortens settling but heats the winding and may push the instrument out of its comfortable range.
Resistance is a property of the conductor, and conductor resistance changes with temperature. Around 20 °C, copper changes by roughly 0.39% per °C; aluminium is similar at about 0.40% per °C. A 10 °C error in the assumed temperature produces about a 4% error in the result - larger than the accuracy of most instruments. These coefficients are approximations near ambient; over a wide temperature range the relationship is not perfectly linear.
R(ref) = R(t) x (K + T(ref)) / (K + t)
K is the inferred absolute-zero constant for the conductor material: 235 for copper and 225 for aluminium in the IEC convention used here. IEEE C57.12.90 commonly uses 234.5 for copper. Both are accepted, but the same constant must be used throughout a comparison, and the method should be stated in the report. T(ref) is the reference temperature required by your standard or specification - 75 °C is common for oil-immersed power transformers, but it is not universal; dry-type units use references tied to their insulation class, and some specifications call for a different value. Example: 0.500 Ω measured at 45 °C, corrected to 75 °C: R = 0.500 x (235 + 75) / (235 + 45) = 0.554 Ω, about 10.7% higher.
It is the winding temperature, not the ambient temperature and not automatically the top-oil temperature. After a transformer has been carrying load and is switched off, the winding is hotter than the oil, and the difference takes time to equalise. Two defensible methods:
Whichever method is used, apply it the same way every time and state it in the report. A consistent small bias is easier to interpret than a random one, and a change of method between tests can look like a change in the winding.
The core remembers. A previous DC test, a resistance measurement, or a normal shutdown can leave residual flux, and that changes how quickly the winding reaches a steady current. The symptom is a reading that settles at a different value than last time, or takes much longer to settle.
It is worth separating three things that are often confused:
Do not conclude "residual magnetism" from a forward/reverse difference alone. A difference indicates an offset, and the cause of that offset needs its own investigation.
Windings in the same transformer are magnetically coupled. What you measure on one phase depends on how the other windings are left - open, shorted or grounded - and on whether the winding is star or delta connected.
Milliohm measurements compete with whatever else is happening in the substation: welding, DC stray currents, high-voltage fields and radio transmitters can all couple into the leads. Signs include a jumping last digit, a reading that changes when someone walks past, or a value that differs between morning and afternoon.
Modern winding resistance testers are accurate, but their specification has structure, and the structure matters at the bottom of a range. A typical statement is +/- (0.2% of reading + 2 digits) on the main ranges, widening to +/- (0.5% + 2 digits) at the top of the range, with a resolution of 0.1 µΩ.
The two terms behave differently. The percentage term scales with the reading; the digit term is fixed by the display resolution. At 1 mΩ on a 0.1 µΩ display, 0.2% is 2 µΩ and 2 digits is 0.2 µΩ, for a total of about 2.2 µΩ - roughly 0.22% of the reading. At 100 µΩ, the same 2 digits are 2% of the reading, which is why low-value measurements demand better connections and a suitable range.
| Source | Typical effect | How to control it |
|---|---|---|
| Temperature assumed, not measured | About 0.4% per °C; a 10 °C error is about 4% | Measure winding or stabilised oil temperature; correct to the stated reference |
| Two-wire connection | Lead and contact resistance add directly; can rival the winding value | Four-wire connection, sense leads inside the current path |
| Reading taken before stabilisation | Several percent low, variable | Wait for the instrument's stable indication |
| Contaminated or loose clips | Unpredictable, often unstable | Clean bare metal, re-clamp, check for heating |
| Test current heating the winding | About 0.4% per °C rise | Shortest practical test, appropriate current range |
| Instrument accuracy | Percentage of reading plus digits, per the datasheet | Valid calibration, range chosen for the value |
| Interference | Last digits, occasionally more | Grounding, twisted leads, averaging, quiet station |
Once the numbers are corrected, the judgement is comparative. Three comparisons carry most of the information: phase to phase at the same tap, tap to tap across the range, and present values against the previous test or the factory baseline.
Imbalance(%) = (R(max) - R(min)) / R(average) x 100
A common field reference is that phase resistances should agree within about 2% after temperature correction. This is a reference example, not an acceptance criterion: the applicable standard, the transformer design, the connection and the customer specification decide the real limit, and different test procedures compare differently - some use the average of three phases, some compare pairwise, some compare against the factory record. A delta-connected winding also needs the conversion method that fits its connection before phases are compared.
Two habits prevent false alarms: compare like with like, and look at the trend before the absolute value. A winding that has moved 1.5% since the last test is more interesting than one sitting 1.5% from a nominal nameplate figure.
| Symptom | Likely cause | First action |
|---|---|---|
| Reading keeps falling | Current still rising; winding not stabilised | Wait for the stable indication; check selected range |
| Reading drifts upward slowly | Winding heating; loose clip heating; ambient change | Shorten the test, re-clamp, shade the set |
| Reading much higher than expected | Two-wire connection, dirty contact, wrong tap, broken strand | Check lead arrangement, clean contacts, verify tap |
| One phase differs noticeably | Tap contact, joint, or genuine winding fault | Repeat the measurement; inspect joints; compare other taps and other tests |
| Display jumps in the last digits | Interference, long unshielded leads, poor ground | Ground the case, shorten or twist leads, use averaging |
| Test never completes | Current cannot be driven through the loop; range too high; lead problem | Check current loop and lead continuity; confirm instrument output; then adjust range |
| Values differ from last year by a few percent | Temperature reference or test conditions changed | Re-correct to the same reference; compare recorded methods |
The winding is still charging. Current rises gradually in an inductive circuit, so the calculated resistance falls until the current stabilises. Wait for the instrument's stable indication. If the value never settles, check that the selected current range can actually drive the winding and that the current loop is sound.
For copper, about 0.39% per °C near ambient; aluminium is similar. A 10 °C error in the assumed winding temperature gives roughly a 4% error, larger than the accuracy of most testers. Record the winding temperature, or a stabilised oil temperature, and state the method.
Not for diagnostic work. A two-wire meter adds lead and contact resistance to the reading, and those terms can be comparable to the winding resistance itself on large transformers. Four-wire measurement is the standard approach because it removes them; the sense leads must be connected inside the current path.
Small differences are normal and come from winding geometry, tap position and test conditions. About 2% is a common field reference, not a universal acceptance limit; the standard, design, connection and customer specification set the real limit. A change since the last test usually matters more than the absolute spread.
Not automatically. Higher current shortens charging and improves resolution on low-resistance windings, but it also heats the winding, and copper resistance rises with temperature. The right current gives a stable reading within an acceptable time without measurable heating, and it must be within the instrument's output capability. The manual defines the valid current and range combinations.
Until the instrument indicates stability; that can range from seconds to several minutes. A fixed wait is not a safe substitute. Record the stabilisation time, because a sudden change in settling time is itself diagnostic.
Winding resistance testers
Related transformer diagnostic instruments (not winding resistance testers)
Send the transformer rating, connection, tap position, measured values and the temperature you used. We will help you separate a measurement problem from a winding problem before you open the unit.
Scope note: this guide describes general practice for DC winding resistance measurement. Acceptance limits, temperature references, the K constant and connection methods come from the applicable standard, the transformer manufacturer's instructions and the customer specification. Values quoted here are typical examples, not universal requirements.